Overview

The Square D 8536 SDG1 is a industrial-grade NEMA Size 2 motor starter engineered for full-voltage starting and stopping of AC squirrel-cage motors in manufacturing and automation environments. With a 45-ampere line rating and 600 VAC system voltage capability, this Type S non-reversing starter (Series A) provides dependable motor control for horsepower ratings up to 25 HP at 460/575 VAC. The unit features a separate control design (Form S) with screw-clamp electrical connections and is suitable for surface mounting in NEMA 1 enclosures.

Key Features

  • 45-Ampere Line Rating: 3 pole NEMA Size 2 non-reversing starter with 45 ampere rating
  • Motor Ratings: 10 HP at 200 VAC, 15 HP at 230 VAC and 25 HP at 460 and 575 VAC
  • Non-Reversing Type S Design: Type S NEMA motor starters are used for full voltage starting and stopping of AC squirrel cage motors
  • Standard Overload Protection: Melting alloy type overload relay that uses Type B thermal units to sense over current conditions
  • Short Circuit Rating: 5 kA maximum SCCR (Short Circuit Current Rating) per UL508A when protected by an appropriate circuit breaker or fuse
  • Flexible Coil Options: Available with replaceable coils in a wide variety of voltages

Technical Specifications

The 8536 SDG1 combines robust construction with standard industrial electrical ratings:

  • Class: 8536 (Magnetic Motor Starter)
  • Type: SDG / Form S (Separate Control Unit)
  • NEMA Size: 2
  • Poles: 3
  • Phase: 3-phase
  • Line Current Rating: 45 Amps
  • System Voltage: 600 VAC
  • Overload Type: Thermal (Type B units with melting alloy relay)
  • Electrical Connection: Screw-clamp terminals
  • Enclosure Rating: Not rated (open device); suitable for NEMA 1 surface-mounted enclosures
  • Manufacturing Origin: United States

Typical Applications

The Square D 8536 SDG1 starter is widely deployed in:

  • Pump and compressor motor control in facilities management
  • Machine tool and manufacturing equipment motor circuits
  • HVAC and industrial process motor starting
  • OEM equipment and panel builders requiring NEMA-rated starters
  • Retrofit and replacement installations in existing control systems

Compatibility & Replacements

Compatible With

  • AC squirrel-cage induction motors rated 10–25 HP (depending on line voltage)
  • 600 VAC three-phase industrial power systems
  • Thermal overload heater packs (Type B units) in the 15A–45A range
  • Standard industrial motor control circuits using separate control units
  • NEMA 1 and open-mounting enclosure installations

Replaces / Drop-In Replacement For

  • Square D 8536 SDG1 variants with different coil voltages (8536SDG1V02, 8536SDG1V03, 8536SDG1V06, etc.)
  • Other Square D Class 8536 Type S non-reversing starters in NEMA Size 2
  • Verify the coil voltage, series designation, and thermal unit range match your application before installing

Works With

  • Separate control circuit supplies (110/120 VAC, 220/240 VAC, or other coil voltages as rated on the unit)
  • Standard industrial push-button stations and selector switches
  • Overload relay heater packs rated for 15–45 amperes
  • Motor circuit branch protection via circuit breakers or fuses (5 kA SCCR minimum recommended)
  • Manual or automated starter controls in plant-floor automation systems
Condition

Used

Manufacturer

Square D / Schneider Electric

Model Number

8536 SDG1

Class

8536

Type

SDG (Non-Reversing)

Series

A

NEMA Size

2

Poles

3

Phase

3-phase

Line Current Rating

45 Amps

System Voltage

600 VAC

Motor Horsepower Ratings

10 HP @ 200 VAC, 15 HP @ 230 VAC, 25 HP @ 460/575 VAC

Overload Type

Thermal (Type B heater units, 15–45 A range)

Short Circuit Rating (SCCR)

5 kA per UL 508A

Electrical Connection

Screw-clamp terminals

Form / Design

S (Separate Control Unit)

Enclosure Type

Open device; NEMA 1 surface-mount rated

Coil Voltage Options

Varies by model variant (110/120 VAC, 220/240 VAC, etc.)

Origin

Made in the USA