Overview

The SG50-F-IR3-AS10 is Teledyne’s Spyglass triple-spectrum infrared flame detector, designed for industrial fire detection where reliability and speed are critical. This detector offers reliable detection of hydrocarbon and non-hydrocarbon fires, including hydrogen, hydrogen/methane blends, ammonia, and silane. The fixed-mount configuration with stainless steel housing (electro-polished 316) delivers NEMA 4X/6P protection suitable for harsh industrial environments, refineries, manufacturing facilities, and hazardous zones.

Key Features

  • Triple-Spectrum IR Detection: Analyzes three distinct infrared wavelengths simultaneously, providing optimized hydrocarbon fire detection and industry-leading false alarm immunity.
  • Fast Response: 40ms detection time for fast burst or explosion, with detection distances up to 100 feet for hydrogen fires.
  • Operational Outputs: 3 relays (Alarm, Auxiliary, Fault) with SPST volt-free contacts rated 2A at 30 VDC; 0-20mA stepped current output in 3-wire and 4-wire configurations; HART rev 7.0 and Modbus RTU compatible.
  • Self-Diagnostics: Built-in-Test (BIT) for automatic and manual self-test of window cleanliness and overall detector operation.
  • Rugged Construction: IP66 & 68 rated enclosure with -55°C to +85°C operating temperature range, rated for up to 99% RH non-condensing humidity.

Technical Specifications

Parameter Specification
Detection Technology Triple Infrared (IR3)
Operating Temperature Range -55°C to +85°C (-67°F to +185°F)
Storage Temperature Range -55°C to +85°C
Humidity Rating Up to 99% RH, non-condensing
Enclosure Rating IP66 & IP68 (2m, 24hr immersion)
Housing Material Stainless Steel 316, Electro-Polished
Dimensions (Detector) 140 x 90 x 90 mm (5.51 x 3.54 x 3.54 inches)
Weight (Detector) 3.0 kg (6.6 lbs)
Weight (Tilt Mount) 1.5 kg (3.3 lbs)
Field of View 90° Horizontal, 75° Vertical
Relay Outputs 3 SPST volt-free relays, 2A at 30 VDC (Alarm, Auxiliary, Fault)
Analog Output 0-20mA stepped current, 3-wire and 4-wire configurations
Communication Protocols HART 7.0, Modbus RTU, RS-485
Compliance FMus, FMc, ATEX, IECEx, UKEX, NFPA33
Sensitivity Levels 5 ranges: Extreme, High, Medium, Low, Very Low
Time Delay 0–30 seconds adjustable

Typical Applications

  • Oil and gas refineries and processing plants
  • LNG and hydrogen production facilities
  • Chemical manufacturing and storage areas
  • Power generation plants and substations
  • Automotive spray paint booths (NFPA33 compliant)
  • Machinery enclosures and equipment protection
  • Hazardous area monitoring in ATEX-regulated zones

Compatibility & Replacements

Compatible With

  • Fire alarm control panels supporting 0-20mA, relay, and HART inputs
  • Building management systems (BMS) with analog and digital inputs
  • PLC and DCS systems with HART communicator modules
  • Modbus RTU networks via RS-485 interface
  • Any control logic accepting volt-free relay contact signals

Replaces / Drop-In Replacement For

Verify compatibility with your system integrator or Teledyne before ordering. The SG50-F-IR3-AS10 variant designation indicates specific output and mounting configurations; ensure your control system supports the output type (0-20mA, relay, HART) prior to replacement.

Works With

  • HART Communicator software for configuration and diagnostics
  • Modbus RTU master devices and industrial networks
  • Legacy fire alarm systems with analog and relay input cards
  • IEC 61508 safety-critical instrumentation systems
  • Teledyne flame simulator kits for testing and commissioning
Detection Technology

Triple Infrared (IR3)

Operating Temperature

-55°C to +85°C (-67°F to +185°F)

Humidity Rating

Up to 99% RH, non-condensing

Enclosure Rating

IP66 & IP68 (2m immersion, 24hr)

Housing Material

Stainless Steel 316, Electro-Polished

Dimensions

140 x 90 x 90 mm (5.51 x 3.54 x 3.54")

Weight (Detector)

3.0 kg (6.6 lbs)

Field of View

90° Horizontal, 75° Vertical

Relay Outputs

3 SPST volt-free, 2A @ 30 VDC

Analog Output

0-20mA stepped current

Communication

HART 7.0, Modbus RTU, RS-485

Compliance

FMus, FMc, ATEX, IECEx, UKEX, NFPA33

Sensitivity Levels

5 ranges (Extreme, High, Medium, Low, Very Low)

Response Time

40ms for fast burst/explosion detection