Overview

The LS Electric MT-32/3K is a 3-pole thermal overload relay designed for motor protection in industrial control systems. Rated for 7-10A operation with Class 10A trip characteristics, this relay provides dependable overcurrent and phase loss protection. The MT-32/3K is part of LS Electric’s Metasol overload relay family, engineered to meet IEC 60947-4-1 and UL 508 standards for critical motor control applications.

Key Features

  • Class 10A Trip Characteristic: Fast and reliable trip response to overload conditions, protecting motors from thermal damage.
  • Phase Loss Sensitivity: Detects single-phase conditions and trips to prevent motor damage during phase failures.
  • Contactor Integration: Direct mounting to MC-9b through MC-40a contactors for compact panel design and simplified wiring.
  • Manual/Automatic Reset: Flexible reset options for manual intervention or automatic restart capability.
  • International Approvals: CE, UL, and CCC certified with Type 2 coordination with MCCB and TOR devices.

Technical Specifications

  • Configuration: 3-pole
  • Current Range: 7-10A
  • Trip Class: 10A (Class 10)
  • Rated Operational Voltage [Ue]: 690V
  • Rated Insulation Voltage [Ui]: 690V
  • Rated Withstand Voltage [Uimp]: 6 kV
  • Frequency Rating: 50/60 Hz
  • Terminal Type: Screw clamp
  • Operating Temperature Range: -5°C to +40°C
  • Protection IP Rating: IP 20
  • Standards Compliance: IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Certifications: CE, UL, CCC, KR, LR, BV, DNV, ABS, NK, RINA
  • Heater Type: 3K (Differential 3-heater)

Typical Applications

The MT-32/3K thermal overload relay is widely used in:

  • Motor control centers (MCCs) and control panels
  • Industrial machinery and production line automation
  • HVAC systems and ventilation control
  • Pump and fan motor protection
  • General-purpose motor starters
  • Type 2 coordination systems with circuit breakers and motor control devices

Compatibility & Replacements

Compatible With

  • LS Electric MC-series contactors (MC-9b through MC-40a)
  • LS Electric UZ-32 auxiliary block assemblies
  • Motor control centers using 690V rated protection devices
  • IEC 60947-compliant motor starter systems
  • Type 2 coordination motor control systems

Replaces / Drop-In Replacement For

Verify compatibility with your system integrator before ordering. The MT-32/3K is the 7-10A variant of the MT-32 series and is not a direct replacement for other current ranges or trip classes (such as 3D or 2H variants).

Works With

  • LS Electric Metasol motor control product line
  • Standard 3-pole motor starter configurations
  • IEC 60947-4-1 compliant protection systems
  • Industrial automation control platforms using motor protection relays
Manufacturer

LS Electric (Metasol)

Part Number

MT-32/3K

Configuration

3-pole

Current Range

7-10A

Trip Class

10A (Class 10)

Rated Voltage (Ue)

690V

Insulation Voltage (Ui)

690V

Withstand Voltage (Uimp)

6 kV

Frequency

50/60 Hz

Terminal Type

Screw clamp

Operating Temperature

-5°C to +40°C

Protection Rating

IP 20

Standards

IEC 60947-4-1, IEC 60947-5-1, UL 508

Certifications

CE, UL, CCC, KR, LR, BV, DNV, ABS, NK, RINA

Reset Type

Manual/Automatic